Newsletter subscribe

MARINE, Marine Modules, Marine Modules - Hochiki

VF6007-0M

vf6007-0m
Posted: February 16, 2015 at 6:28 am   /   by   /   comments (0)

Dual Input Module

marine_approvals2

VF6007-0M Dual Input Module Data Sheet

The VES Dual Monitor Module (VF6007- 0M) is designed for use on the Elite analog addressable system. It provides two independent contact monitoring circuits while only utilizing one address on the SLC loop.

Standard Features

  • Fast, reliable contact monitoring utilizing the VES DCP (Digital Communications Protocol)
  • 127 devices can be used per DCP loop
  • Bi-colored indicating LED provides module status
  • Dual input contact monitor
  • Can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contacts
  • Operates on Class A or Class B SLC loop
  • Accepts up to 14 AWG wire
  • Mounts to 4” square gang box